ISSN:
1089-7623
Source:
AIP Digital Archive
Topics:
Physics
,
Electrical Engineering, Measurement and Control Technology
Notes:
Beam position stability was found to be largely affected by the distortion of the storage ring building, especially when the beam emittance was lowered. Building distortion in the horizontal direction was noticed as the diurnal deviation of the orbit circumference. The deviation was measured by reading the amount of rf frequency variation necessary to recover the horizontal central orbit. The deviation of the orbit circumference was interpreted to be induced from the ring floor expansion. Such diurnal expansion of the ring floor was evaluated by using a model simulation that dealt with the distortion of the ring building under thermal stress. To reduce such thermal stress, the rooftop of the building was insulated. The deviation of the ring circumference measured after insulation was reduced to one-half of that measured before. The simulation also gave the same amount of deviations as measured before and after insulation.
Type of Medium:
Electronic Resource
URL:
http://dx.doi.org/10.1063/1.1142697