Description / Table of Contents:
Contents With the help of certain measurable quantities belonging to the different commutation voltages we can get the firing- or the extinction angles for establishing equidistant valve control. With unusually large asymmetries it will be possible to deviate from these angles with the benefit of obtaining a higher d.c. voltage. Instead of the customary firing angle control, the extinction angle control is recommended, as this completely eliminates the influence of the current controller on the extinction angle of the inverter.
Notes:
Übersicht Netzspannungsbedingte Unsymmetrien bei HGÜ-Stromrichtern lassen sich durch Zusatzsignale, die von den individuellen Kommutierungsspannungen abgeleitet werden, reduzieren, so daß sich äquidistante Zündimpulse ergeben. Bei ungewöhnlich großen Unsymmetrien kann von diesen Winkeln zur Erreichung höherer Gleichspannung abgewichen werden. An Stelle der bisher allgemein verwendeten Zündwinkelsteuerung wird beim Wechselrichter eine Löschwinkelsteuerung empfohlen, da sie den Einfluß des Stromreglers auf den minimalen Löschwinkel des Wechselrichters beseitigt.