Deterioration of timber in cooling towers. Possible causesTimber in cooling towers is always exposed to exacting working conditions and shows many signs of deterioration. In order to clarify two specific cases of deterioration, the timber of cooling towers (redwood and fir) has been subjected to mechanical tests for loss of mechanical strength whilst the cooling water and circulating water have been analyzed. It was found that alkaline water with iron content causes a marked loss of mechanical strength and that the impregnation of the wood with tar oils has a very great protective effect as it inhibits the corrosion caused by iron nails.
Notes:
Holz, das durchgängig in Kühltürmen harten Betriebsbedingungen ausgesetzt ist, zeigt vielartige Schäden. Zur Aufklärung zweier Schadensfälle wurde das Holz von Kühltürmen (Redwood u. Fichte) mechanisch auf Wertminderung (Steifigkeits-Einbuße) sowie das Kühlwasser und das Umlaufwasser analytisch untersucht. Festgestellt wurde, daß alkalische, eisenhaltige Wässer zu starkem Steifigkeitsverlust (Schwächung) führen und, daß Imprägnieren des Holzes mit Teerölen in hohem Maße zerstörungsschü;tzend wirkt, da dies auf die Korrosion eiserner Nägel inhibierend wirkt.